Specifications
Solenoid Enclosures: Valves listed in this series have Red-Hat II
molded epoxy solenoids. Red-Hat II valves are identified by the change
letter "G" and "H" in their catalog numbers, e.g.,
8345G1 or 8345H1, and are shown in red.
Standard Enclosures:
Red-Hat II -- Types 1, 2, 3, 3S, 4 and 4X Combination General Purpose
and Watertight
Optional Enclosures:
Red-Hat II -- Types 3, 3S, 4, 4X, 6, 6P, 7 and 9 Combination
Explosionproof and Watertight. To order, add prefix "EF" to
catalog number.
Additional constructions are available. The Optional
Features Section contains descriptions and ordering information for:
Open Frame Solenoids · Junction Box Enclosures · Panel Mount
Constructions.
|
Electrical: Standard Voltages: 24, 120, 240, 480 volts, AC, 60 Hz
(or 110, 220 volts, AC, 50 Hz)
6, 12, 24, 120, 240 volts, DC
Other voltages are available when required.
Coil: Continuous duty molded Class F.
Nominal Ambient Temperature Ranges: AC Construction: 32°F to 125°F.
DC Construction: 32°F to 104°F.
| IMPORTANT: A
minimum operating pressure differential must be maintained
between the pressure and exhaust ports. Supply and exhaust
piping must be full area, unrestricted. ASCO flow controls and
other similar components must be installed in the cylinder lines
only. |
|
Valve Parts in Contact with Fluids:
Body -- Brass or 316 S.S., as listed
Seals and Disc -- Buna "N" and Nylon
Core Tube -- 305 s.s.
Core and Plugnut -- 430F s.s.
Springs -- 302 s.s.
Shading Coil -- Copper
Piston -- Nylon
Leakage: Liquids: none;
Air: slight leakage through exhaust when energized.
Approvals: CSA certified. UL listed as General Purpose Valve.
Ordering Information: Important: We must have catalog
number, voltage and Hertz, operating pressure and fluid handled. Use
strainers with Solenoid Valves.
|